Alternate Operation Relay 61F-AN / -APN2

• Electronic Relay with the same operation as the G4Q Latching Relay. Compared with the G4Q, the 61F-AN/-APN2 has a shorter power supply application time and no restrictions on mounting direction.

• Compact Models (61F-AN) and Compact Plug-in Models (61FAPN2) available.

Note: A changeover switch must be included in the sequence to enable operating only one pump.

Description

Ratings

 

Supply voltage 100, 110, 200, 220 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
Power consumption 3 VA
Accessories Hold-down clip PFC-N8 *

 

* Hold-down clip PFC-N8 is attached only 61F-APN2.

Contact Ratings (with G2RK Keep Relay)

 

Item Resistive load (cosΦ = 1) Inductive load (cosΦ = 0.4, L/R = 7 ms)
Max. load 3 A at 250 VAC 1.5 A at 250 VAC
Carry contact 0.125
Max. operating current 0.125
Max. switching capacity 750 VA 375 VA

 

Characteristics

 

Response time Operate: 25 ms max.
Release: 30 ms max.
Minimum pulse width Min. ON time: 40 ms min.
Min. OFF time: 200 ms min.
Insulation resistance 100 MΩ min. at 500 VDC (between each terminal and power supply)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between each terminal and power supply)
Vibration resistance 10 to 55 Hz, 1-mm double amplitude
Shock resistance 10 G (approx. 98 m/s2)
Life expectancy Mechanical: 1,000,000 operations (at operating frequency of 1,800 operations/hour)
Electrical: 100,000 operations min.
(rated load)
Ambient temperature Operating: -10 to 55°C
Ambient humidity Operating: 45% to 85% RH
Weight 61F-AN: Approx. 215 g
61F-APN2: Approx. 190 g

Reviews

There are no reviews yet.

Be the first to review “Alternate Operation Relay 61F-AN / -APN2”