Description
61F-GPN-BT | 61F-GPN-BC | |
---|---|---|
Rated voltage | 24 VDC | |
Allowable voltage range | 85% to 110% of the rated voltage | |
Interelectrode voltage | 5 VAC max. | |
Operation resistance *1 | Variable (0 to 100 kΩ) | |
Error | For scale of 0: +10 kΩ; For scale of 100: ±10 kΩ | |
Release resistance | 200% max. of the operation resistance | |
Switching between supply and drainage |
Terminals 7 and 8 open: Automatic drainage operation Terminals 7 and 8 shorted: Automatic supply operation |
|
Output specifications | Open collector (NPN) 30 VDC, 100 mA max. Leak current: 100 μ A max. |
Relay output, SPST-NO 5 A, 240 VAC (Resistive load) 5 A, 30 VDC |
Life expectancy | — | Electrical: 100,000 operations min. Mechanical: 20,000,000 operations min. |
Accessories | Hold-down clip PFC-N8 | |
Wiring distance *2 | 100 m max. |
*1. The 61F may not operate at resistance settings close to zero. Adjust the sensitivity to match actual usage conditions.
*2. The figure for wiring distance above is for when 600-V 3-core cabtire cable with a cross-sectional area of 0.75 mm2
is used.
*2. The figure for wiring distance above is for when 600-V 3-core cabtire cable with a cross-sectional area of 0.75 mm2
is used.
Characteristics
Ambient operating temperature | -10 to 55°C |
---|---|
Ambient operating humidity | 25% to 85% |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength * | 2,000 VAC, 50/60 Hz for 1 minute |
Power consumption | 2 W max. |
Response time | Operating: 1.5 s max. Releasing: 3.0 s max. |
Approved standards | UL61010-1, CAN/CSA C22.2 No.61010-1 EN61010-1 EN61326-1 Industrial electromagnetic environment |