Description
Power supply voltage | 24 VAC 50/60 Hz or 24 VDC 100 to 240 VAC 50/60 Hz |
---|---|
Voltage across elec-trodes | 5 V p-p (Approx. 20 Hz) |
Power consumption | 24 VAC/DC: 2.0 VA/1.1 W max. 100 to 240 VAC: 4.6 VA max. |
Operating resistance | 10 k to 100 kΩ (variable) |
Reset resistance | 250 kΩ max. |
Response time | Approx. 0.1 to 10 s (variable) |
Length of cable | 100 m max. (fully insulated 3-core 0.75-mm2 cab-tyre cable, 600 V) |
Indicators | PWR: Green, RY: Yellow |
Output contact ratings | Rated load Resistive load 5 A at 250 VAC 5 A at 30 VDC Maximum switching capacity: 1,250 VA, 150 W Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC/30 VDC: 100,000 operations |
Ambient operating tem-perature | -20 to 60°C (with no condensation or icing) |
Storage temperature | -25 to 65°C (with no condensation or icing) |
Ambient humidity | 25% to 85% (with no condensation) |
Storage humidity | 25% to 85% (with no condensation) |
Altitude | 2,000 m max. |
Terminal screw tightening torque | 0.49 to 0.59 N·m |
Case color | N1.5 |
Case material | PC and ABS, UL 94 V-0 |
Weight | Approx. 150 g |
Mounting | Mounts to DIN Track. |
Dimensions | 22.5 × 90 × 100 mm (W × D × H) |
Specifications
Operating voltage range | 85% to 110% of rated voltage |
---|---|
Installation environ-ment | Installation category II, pollution level 2 |
Approved standards | EN 61010-1 |
EMC | EN 61326-1 Industrial electromagnetic environment |
Safety standards | UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA: C22.2 No.14, CCC: GB/T 14048.5 |
Insulation resistance | 20 MΩ min. Between all external terminals and the case Between all power supply terminals and all input terminals Between all power supply terminals and all output terminals Between all input terminals and all output termi-nals |
Dielectric strength | 2,000 VAC for 1 min Between all external terminals and the case Between all power supply terminals and all input terminals Between all power supply terminals and all output terminals Between all input terminals and all output termi-nals |
Noise immunity | 1,500 V power supply terminal common/normal mode Square-wave noise of ±1-μs/100-ns pulse width with 1-ns rise time |
Vibration resistance | Frequency: 10 to 55 Hz, 0.35-mm single amplitude 10 sweeps of 5 min each in X,Y, and Z directions |
Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes |
Degree of protection | Terminals: IP20 |
Reviews