Description
Approved Standards
Agency | Standard | File No. |
---|---|---|
UL | UL508 | E76675 |
CSA | CSA C22.2 No.14 | LR45746 |
CCC (CQC) | GB/T14048.5 | Contact your OMRON representative for details. |
Note: 1. Models XE, XV, and XV2 are not approved by UL, CSA, and CCC.
2. Ask your OMRON representative for information on approved models.
2. Ask your OMRON representative for information on approved models.
Ratings
Model | Rated voltage | Non-inductive load (A) | Inductive load (A) | ||||||
---|---|---|---|---|---|---|---|---|---|
Resistive load | Lamp load | Inductive load | Motor load | ||||||
NC | NO | NC | NO | NC | NO | NC | NO | ||
ZE-[] ZV-[] ZV2-[] |
125 VAC 250 VAC 480 VAC |
15 15 10 |
3 2.5 1.5 |
1.5 1.25 0.75 |
15 15 6 |
5 3 1.5 |
2.5 1.5 0.75 |
||
125 VDC 250 VDC |
0.5 0.25 |
0.5 0.25 |
0.05 0.03 |
0.05 0.03 |
|||||
XE-[] XV-[] XV2-[] |
8 VDC 14 VDC 30 VDC 125 VDC 250 VDC |
10 10 10 10 3 |
3 3 3 3 1.5 |
1.5 1.5 1.5 1.5 0.75 |
10 10 10 7.5 2 |
10 10 10 6 1.5 |
5 5 5 2 2 |
2.5 2.5 2.5 2.5 1.5 |
Note: 1. The above figures are for standard currents.
2. Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
3. Lamp load has an inrush current of 10 times the steadystate current.
4. Motor load has an inrush current of 6 times the steady-state current.
2. Inductive loads have a power factor of 0.4 min. (AC) and a time constant of 7 ms max. (DC).
3. Lamp load has an inrush current of 10 times the steadystate current.
4. Motor load has an inrush current of 6 times the steady-state current.
Inrush current | NC | 30 A max. |
---|---|---|
NO | 15 A max. |
Approved Standard Ratings
UL/CSA
Model | Rated voltage | Current | Horsepower |
---|---|---|---|
ZE | 125 VAC 250 VAC 480 VAC |
15 A 15 A 15 A |
1/8HP 1/4HP |
125 VDC 250 VDC |
0.5 A 0.25 A |
— |
CCC (GB/T14048.5)
Applicable category and ratings |
---|
AC-12 10 A/250 VAC |
Characteristics
Degree of protection | IP65 *1 | |
---|---|---|
Durability *2 | Mechanical | Z[]: 10,000,000 operations min. X[]: 1,000,000 operations min. |
Electrical | Z[]: 500,000 operations min., for 15 A, 250 VAC resistive load X[]: 100,000 operations min., for 10 A, 125 VDC resistive load |
|
Operating speed | Plunger type: 0.01 mm/s to 0.5 m/s Lever type: 0.02 mm/s to 0.5 m/s |
|
Operating frequency | Mechanical | 120 operations/min |
Electrical | 20 operations/min | |
Rated frequency | 50/60 Hz | |
Insulation resistance | 100 MΩ min. (at 500 VDC) | |
Contact resistance | 15 mΩ max. (initial value) | |
Terminal temperature rise | 50°C max. | |
Dielectric strength | Between terminals of the same polarity |
1,000 VAC, 50/60 Hz for 1 min |
Between current-carrying metal part and ground |
Z[]: 2,000 VAC, 50/60 Hz for 1 min X[]: 1,500 VAC, 50/60 Hz for 1 min |
|
Between each terminal and non-current-carrying metal part |
Z[]: 2,000 VAC, 50/60 Hz for 1 min X[]: 1,500 VAC, 50/60 Hz for 1 min |
|
Vibration resistance | Malfunction | 10 to 55 Hz, 1.5-mm double amplitude *3 |
Shock resistance *3 |
Destruction | 1,000m/s2 max. |
Malfunction | 100 m/s2 max. *4 50 m/s2 max. *5 |
|
Ambient operating temperature | -10°C to +80°C (with no icing) | |
Ambient operating humidity | General-purpose type: 35% to 85%RH Sealed type: 35% to 95%RH |
|
Weight | Approx. 260 to 280 g |
Reviews